Red Fail Fault was not properly identified, MMU2-1600G, MMU2-1600GE

Originally posted 10/10/2018
Product
MMU2-1600G, MMU2-1600GE
Scope
This bulletin applies only to MMU-1600G and MMU2-1600G with or without the Ethernet port. (E option).
Issue
Red Fail Fault was not properly identified in Type 12 cabinets with FYA Enabled on Non-FYA Channels.
Root Cause
In a Type 12 cabinet a Red Fail Fault was not indicated on Non-FYA channels when all the voltages of the channel were below their OFF Threshold.
Operational
If a channel met all the conditions in the root cause the MMU will continue to operate normally and will not go into fault.
Corrective Action
Upgrade to Firmware version 02.00.05 or greater.
For questions regarding this Service Bulletin, please contact EDI Technical Support at, support@editraffic.com.