[CALTRANS] How do I activate Dual Indication on a Caltrans 33X Series Cabinet?
See the video below for information on activating Dual Indication on your EDI signal monitor.
This video explains how to enable green/yellow dual-indication monitoring when using a 2010ECL or 2018KCL monitor in a 332 cabinet that does not monitor red indications.
1. Understand the Issue
- A traditional 210 monitor does not detect green/yellow dual indications by default.
- If a yellow indication is stuck while the phase is displaying green, the monitor will not immediately enter a fault.
- When the controller transitions to another phase, the monitor may detect a conflict and enter a fault.
Example: A stuck yellow on phase 2 may result in a conflict involving channels 2, 4, and 10 when transitioning to phases 3 and 7.
2. Enable Dual-Indication Monitoring on a 2010ECL
- Remove the monitor from the cabinet.
- Locate DIP switch 4 (Green/Yellow Enable).
- Turn DIP switch 4 ON.
- Reinstall the monitor.
- The monitor will now detect simultaneous green and yellow indications.
3. Enable Dual-Indication Monitoring on a 2018 KCL
- Use MonitorKey to enable the Green/Yellow Enable setting.
- Install the programmed key in the cabinet.
- Press and hold RESET to apply the configuration.
- The monitor will now detect simultaneous green and yellow indications.
Enabling Green/Yellow Enable allows the monitor to detect simultaneous green and yellow outputs rather than waiting for a phase transition to trigger a conflict fault.