How To Set Up Flashing Yellow Arrow Mode B On The MMU2-16LE For An ATSI Test
- When dialog box appears on PC “insert the program card for FYA EDI MODE B”
- Remove blank MMU card from MMU under test and insert FYA Mode B card programmed for 8 phase flashing yellow arrow
- Select OK on PC
- When the dialog box appears on the PC the MMU powers up and needs to be set up for the FYA portion of testing
- Select copy from program card
- Push next and then select “menu”
- Use next to get cursor to “set/view config” and select
- Use next to get to “Flashing Yellow Arrow” (near end of list) and select
- Select FYA MODE B
- Enable ChPair mode A
- ch 1-13=on
- ch 3-14=on
- ch 5-15=on
- ch 7-16=on
- Push exit
- Enable RY Inp Mode B
- Ch 1 R&Y input=off
- Ch 3 R&Y input=off
- Ch 5 R&Y input=off
- Ch 7 R&Y input=off
- Push Exit
- Flashrate fault=on
- FYA trap detect=on
- Select exit Hit Set and select
- Use next to get to “set-up wizard” and select
- Hit next to begin wizard
- Select unused channels (none for testing purposes) hit exit
- Select next
- Are ped don’t walk signals monitored? Select yes
- Use next to select channel and select to set monitoring (ch 9-12 set for ped monitoring)
- Hit exit
- Select next
- Select prot-perm turns (none for testing purposes)
- Hit exit
- Select next
- Review assignments
- Hit exit
- Select set
- Should see new perams set for : dual ind ,red fail, MYRC, & field check
- Hit exit three times
- Select OK on PC
- Test should complete with failure count =0
- Save PDF version of MMU certification report to file of choice on PC (make sure and note of the testing year in file heading)
- Attach MMU2 paper report to MMU (best to fold into quarters and tape to top of MMU)