Procedure for Reno MMU-1600 D or DE ATSI Test

Standard Test

  1. Enter MMU-1600, or MMU-1600D-DE Monitor data into Monitor Info (serial number, etc.)
    1. Set all “FIELD CHECK” and “DUAL-ENABLES” dip switch to the ON position
    2. Set all “OPTIONS” Dip switch to off
  2. Insert “Regular Test Card” No Jumpers
  3. Start test (make sure you Reset Monitor for 5 sec after setting switches). Tester will “beep” when complete.

Set Up ATSI Tester

  1. On the software click on “Monitor Info” and fill it out. Hit OK.
  2. Next go to “Test Setup” and select NEMA TS2 Monitor Type 16 Channel (If MMU) or 16 Channel MMU2 FYA (if MMU2).
  3. Select “Test Type” Certification hit OK.