Procedure for Reno MMU-1600 D or DE ATSI Test
Standard Test
- Enter MMU-1600, or MMU-1600D-DE Monitor data into Monitor Info (serial number, etc.)
- Set all “FIELD CHECK” and “DUAL-ENABLES” dip switch to the ON position
- Set all “OPTIONS” Dip switch to off
- Insert “Regular Test Card” No Jumpers
- Start test (make sure you Reset Monitor for 5 sec after setting switches). Tester will “beep” when complete.
Set Up ATSI Tester
- On the software click on “Monitor Info” and fill it out. Hit OK.
- Next go to “Test Setup” and select NEMA TS2 Monitor Type 16 Channel (If MMU) or 16 Channel MMU2 FYA (if MMU2).
- Select “Test Type” Certification hit OK.